Program Description
Initial
Condition
15 Fire Lamp
In case of a Fire Alarm the relay is switched on/off
twice per second in mode ‘On for .25s and Off for
.25s’
In case of a Fire Prealarm the relay is switched
on/off once per second in mode ‘On for .25s and
Off for .75s’
In case of a Trouble the relay is switched on/off
once per 2 seconds in mode ‘On for .25s and Off
for 1.75s’
If all the alarm loops related with the relay are
armed the relay is switched on
Otherwise, the relay is switched off
*
16 Alarm Output 2
If all the alarm loops related to the relay are armed
or disarmed (that is, there is neither Intruder
Alarm, nor Silent Alarm, nor Entrance Alarm, nor
Fire Alarm, nor Trouble, nor Arming Failed condi-
tion) the relay is switched on, otherwise the relay
is switches off
*
17
Switch On For a Time
Before Arming
If the related alarm loop is being armed (the Arm-
ing Delay has not yet expired) the relay is
switched on for a given time
Off
18
Switch Off For a Time
Before Arming
If the related alarm loop is being armed (the Arm-
ing Delay has not yet expired) the relay is
switched off for a given time
On
19
Switch On For a Time
Upon Arming
If any related alarm loop has just been armed the
relay is switched on for a given time
Off
20
Switch Off For a Time
Upon Arming
If any related alarm loop has just been armed the
relay is switched off for a given time
On
21
Switch On For a Time
Upon Disarming
If any related alarm loop has just been disarmed
the relay is switched on for a given time
Off
22
Switch Off For a Time
Upon Disarming
If any related alarm loop has just been disarmed
the relay is switched off for a given time
On
23
Switch On For a Time
When Arming Failed
If arming of any related alarm loop has just failed
the relay is switched on for a given time
Off
24
Switch Off For a Time
When Arming Failed
If arming of any related alarm loop has just failed
the relay is switched off for a given time
On
25
Switch On for a Time
Upon Auxiliary Loop
Breaking
If there is an Auxiliary Alarm the relay is switched
on for a given time
Off
26
Switch Off for a Time
Upon Auxiliary Loop
Breaking
If there is an Auxiliary Alarm the relay is switched
off for a given time
On
27
Switch On
Upon Disarming
If at least one related loop is disarmed the relay is
switched on
Off
28
Switch Off
Upon Disarming
If at least one related loop is disarmed the relay is
switched off
On