INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
32
Parameter Description Range
Interface
Response Delay
Defines the value of delay for the
device to response for the net
controller request that has been
received through the interface
RS-485
From 1,5 ms to
500 ms in incre-
ments of 1/8 s
4.3.1 Voltage Analysis
The parameter "Voltage Analysis" defines the condition for device
transition the “Power Failed” mode, whether this condition deals with any
one input voltage trouble or both.
If this parameter is set on the device transits the “Power Failed” mode
when any input voltage has fallen below 10 V and returns back to the op-
erating mode when both input voltages have exceeded 11 V.
If this parameter is set off the device keeps the operating mode until
both input voltage had fallen below 10 V. In such a case the device transits
the “Power Failed” mode and returns back to the operating mode when at
least one input voltage has exceeded 11 V.
4.3.2 Net Address
The “Net Address” parameter is intended to uniquely identify the de-
vice when operating as a part of “Orion” safety system. In such operation
mode the device can transmit messages and receive the commands from
the net controller, being addressed only by means of this unique network
number.
4.3.3 Interface Response Delay
The “Interface Response Delay” parameter is used in case of com-
plicated net configuration taking place when the data transmission can be
delayed, e.g. in case of RS-485 interface conversion to the other interface
types designed for local network, fiber-optic or radio communications.
The current values of “Net Address” and “Interface Response De-
lay” parameters can be reset to default ones by means of three long and
one short tamper pressings. Long pressing means holding during no less
then 1,5 s. Short pressing means holding duration from 0,1 to 0,5 s. Pause
between pressings shall stretch from 0,1 up to 0,5 s.
To adjust the device for the specific application and for it more effec-
tive operating any parameter (such as loop or relay one or device setting)
can be changed by means of "UPROG.EXE" program or ARM Orion Data-
base Administrator program (see section 5.1.4).