INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
30
№ Program name Program description Initial
status
26
‘Turn off for a given
time when auxiliary
alarm’
If at least one loop is in the state ‘Auxil-
iary alarm’ switches the relay OFF for a
given time
ON
27
‘Turn on when
disarmed’
Turn the relay ON if at least one as-
signed alarm loop is disarmed
OFF
28
‘Turn off when
disarmed’
Turn the relay OFF if at least one as-
signed alarm loop is disarmed
ON
29
‘Turn on when
armed’
Turn the relay ON if at least one as-
signed alarm loop is armed
OFF
30
‘Turn off when
armed’
Turn the relay OFF if at least one as-
signed alarm loop is armed
ON
31
‘Turn on when aux-
iliary alarm’
In case of ‘Auxiliary alarm’ turns the relay
ON
OFF
32
‘Turn off when aux-
iliary alarm’
In case of ‘Auxiliary alarm’ turns the relay
OFF
ON
33
‘ASPT-1’ If the alarm loop has entered the ‘Fire
alarm’ status and there are no broken
auxiliary loops then switches the relay
ON for a given time
If an auxiliary loop has broken during the
relay control delay then when recovering
the output will be turned ON for a given
time (the auxiliary loop breaking holds
the turning on delay counting)
OFF
34
‘ASPT-A’ If at least two assigned alarm loops have
entered the ‘Fire alarm’ status and there
are no broken auxiliary loops then
switches the relay ON for a given time
In case of broken auxiliary loop the
switching has blocked and the relay has
remained OFF even after loop recovering
OFF
35
‘ASPT-A1’ If there is alarm loop having ‘Fire alarm’
status and there are no broken auxiliary
loops then switches the relay ON for a
given time
In case of broken auxiliary loop the
switching has blocked and the relay has
remained OFF even after loop recovering
OFF